Titre: | A new PMU based power swing detector to enhance reliability of distance relay |
Auteur(s): | Bentarzi, Hamid Ouadi, Abderrahmane Maun, Jean Claude |
Mots-clés: | Protection System Distance relay Reliability PMU Power Swing detector Blocking Protection Function Symmetrical or asymmetrical faults |
Date de publication: | 2014 |
Collection/Numéro: | CIGRE Session 2014;pp. 1-8 |
Résumé: | Power grid protection aim is to make the generation, transmission and distribution of electrical energy
as safe as possible from the effects of equipment failures. The operational security of the power
system depends on the successful operation of the thousands of relays that protect power elements and
hence protect the whole system against cascading failures. Thus, the failure of a relay to operate as
intended may place at risk the entire power system and its elements.
In conventional transmission line protection, a distance relay is used to provide the primary as well as
backup protection. The voltage and current phasors measurement needed by the distance relay for
determining the impedance may be affected by the power disturbances such as power swing.
Consequently, this power swing may cause mal-operation of Zone three distance relays which in turn
may affect on the reliability of the whole protective scheme. The mal-operation of this relay is
generally due to not only unnecessary tripping during power swing that reduces the security of
protection system and hence its reliability but also unnecessary blocking when symmetrical fault
occurs accompanying a power swing. This latter action may affect on a dependability of the relay and
hence its reliability.
Many techniques have been developed to mitigate these effects and hence improve the relay
reliability. One of the earliest techniques is the using of a negative sequence current magnitude and a
derivative of current angle. This technique is very fast and its test results were promising in blocking
false trip signals during power swing but when it is associated only with unsymmetrical faults. A
combination of waveform of swing center’s voltage (WSCV) and synthetic negative vector has been
also utilized to block the tripping signals during power swing. The technique seems to be rigorous
indiscriminating power swing and high fault resistance. However, it requires two computationally
heavy steps of derivative operation. There is also a time delay of about 30-40 ms before a power swing
blocking scheme can be activated and hence the method is relatively slow.
In order to improve the reliability of the relay, this work proposes a new scheme based on power
swing detector using Phasor Measurement Units (PMUs). In addition to the local phasors information,
the proposed scheme requires remote phasors information from different locations, which can be
provided at high speed by PMUs. These measurements are used for calculating the power and the
difference in phase voltages angles that may be used for detecting power swing and distinguishing it
from the fault. This detector will not block relay when the power swing associated with any fault
types. The MHO relay including power swing detector has been implemented using Simulink block
set and S-function. To validate the present work, the performance of developed relay has been tested
by signals generated by power network Simulink model running under different conditions. The test
results show that this relay provides good discrimination between the transient high currents and the
fault current |