Titre: | Power transformer differential relay reliability assessment using false trip root cause analysis |
Auteur(s): | Zitouni, Abdelkader |
Mots-clés: | Differential Protection False Trip Dependability Security Reliability RCA FTA |
Date de publication: | 2020 |
Editeur: | IEEE |
Collection/Numéro: | 2020 International Conference on Electrical Engineering (ICEE);pp. 1-5 |
Résumé: | Power transformer is vital element in power grid. Its
failure may affect on the continuity of supply of electrical energy
to the consumers. A differential relay, which is generally used for
protecting this power transformer, may be affected by the
disturbances such as inrush current, current transformer
saturation and over-excitation due to external faults.
Accordingly, false trips (mal-operation) of protection system may
be resulted in. This research work proposes root cause analysis
based on fault tree analysis to be used for assessing disturbances
that lead to false trips. When the critical root causes are
identified, mitigation measures are used. The model of security
can help to quantify analytically the reliability of the considered
protection system |