DSpace
 

Depot Institutionnel de l'UMBB >
Publications Scientifiques >
Communications Internationales >

Veuillez utiliser cette adresse pour citer ce document : http://dlibrary.univ-boumerdes.dz:8080/handle/123456789/6650

Titre: Impact of STATCOM on generator positive-offset mho element loss of excitation protection(
Auteur(s): Mati, Ayache
Bentarzi, Hamid
Mots-clés: Loss of Excitation (LOE)
Partial LOE
Total LOE
Date de publication: 2017
Editeur: IEEE
Collection/Numéro: 2017 5th International Conference on Electrical Engineering - Boumerdes (ICEE-B);
Résumé: In this paper simulation studies have been conducted using Simulink/MATLAB software in order to investigate the impact of STATCOM on the positive-offset mho element loss of excitation (LOE) protection scheme in synchronous generator. The obtained results show that the operation of the positive-offset protection scheme takes more time under the integration of STATCOM in the transmission line. Moreover, an under reach phenomena may occur under partial loss of excitation (PLOE) condition of a generator with lightly loading
URI/URL: https://ieeexplore.ieee.org/document/8192156
http://dlibrary.univ-boumerdes.dz:8080/handle/123456789/6650
ISBN: 978-1-5386-0687-2
Collection(s) :Communications Internationales

Fichier(s) constituant ce document :

Fichier Description TailleFormat
Impact of STATCOM on generator positive-offset mho element loss of excitation protection(.pdf573,12 kBAdobe PDFVoir/Ouvrir