Titre: | Conception and implementation of single and simultaneous two diodes open faults automatic detection and localization algorithm in six diodes three phase rectifier bridge |
Auteur(s): | Benslimane, Tarak |
Mots-clés: | Alternative current Fault diagnosis Min and max value Six diodes three phase voltage rectifier Zero harmonic component |
Date de publication: | 2008 |
Collection/Numéro: | Tamkang Journal of Science and Engineering/ Vol.11, N°4 (2008);pp. 367-374 |
Résumé: | The faulty performance of six diodes three phase rectifier is studied under one and two simultaneous open-diodes conditions. This rectifier is feeding a resistive load. The rectifier three phases currents zero harmonic components and their maximum and minimum values are used as diagnostic indices. A knowledge algorithm is based to get information on which IGBT is in open-switch fault condition. This algorithm testing shows that the system could not only detect the open-switch fault, but also identify the faulty switches. Presented simulation results confirm the effectiveness of the proposed methodology |